    kWh vs kW: battery capacity, power and duration explained

    A battery has two headline numbers: power, in kilowatts or megawatts, says how fast it can deliver electricity, and energy capacity, in kilowatt-hours or megawatt-hours, says how much it holds.[1][2] Dividing energy by power gives duration, the hours a battery can run at full output, which is why a 100 MW, 129 MWh grid battery lasts about 75 minutes flat out.[3][4]

    Editor reviewedUpdated Explainer20 claims · 95% primaryBatteries and energy storage, Energy and climate
    Reading level: 3 passages differ; the rest is the same for everyone.

    Every battery spec sheet, from a home backup unit to a grid-scale plant, rests on two different units. Power, measured in watts and kilowatts, is a rate. Energy, measured in watt-hours and kilowatt-hours, is an amount.[5][1] This page sets out the vocabulary the rest of the energy storage pages assume.

    Power and energy

    Think of a water tank. The size of the tap is power: how fast water can come out. The size of the tank is energy: how much water there is in total. Electric power is measured in watts. One kilowatt (kW) is 1,000 watts, and one megawatt (MW) is 1,000 kilowatts.[5] Energy is power multiplied by time. One kilowatt-hour (kWh) is one kilowatt delivered for one hour.[1] A 40-watt light bulb left on for five hours uses 200 watt-hours, or 0.2 kWh.[6]

    Power (W, kW, MW, GW) is an instantaneous rate; energy (Wh, kWh, MWh, GWh) is its integral over time.[1] Storage ratings follow the same split. The US Energy Information Administration (EIA) defines a site’s energy capacity as the maximum energy it can store and its power capacity as the maximum power it can deliver at any moment. At the end of 2019, US large-scale batteries totalled 1,022 MW of power capacity and 1,688 MWh of energy capacity.[2] Home systems are rated the same way, in kW and kWh.[7]

    Duration: how long a battery can run

    Divide a battery’s energy by its power and you get its duration: how many hours it can run at full output.[3] South Australia’s Hornsdale Power Reserve was rated at 100 MW of discharge and 129 MWh of storage in its original form, which works out to about 75 minutes at full power.[4]

    EIA computes duration as nameplate energy capacity (MWh) divided by nameplate power capacity (MW).[3] The Hornsdale Power Reserve, at 100 MW and 129 MWh, came to about 75 minutes at full discharge. Its charge rating, 80 MW, was lower than its discharge rating, so power is not always symmetric.[4] At the other end of the range, Rongke Power’s 200 MW / 1 GWh flow battery runs about five hours.[8] Form Energy says its iron-air system can discharge for up to 100 hours.[9] Flow batteries make the trade-off explicit: bigger tanks add energy and a bigger reactor adds power.[10]

    Why some batteries are built for power and others for energy

    Different jobs need different shapes. In 2019, batteries in the PJM market in the eastern US averaged 10.8 MW of power but only 6.8 MWh of energy, a 45-minute duration. Batteries in California’s CAISO market averaged 4.7 MW and 14.4 MWh, a 4.0-hour duration.[11] EIA calls the PJM fleet power-oriented, built for frequency regulation, and the California fleet energy-oriented, built for reliability.[12] Market rules shape that choice. The California Public Utilities Commission counts a resource toward reliability reserves only if it can provide at least four hours of output.[13]

    Durations have been getting longer. The weighted average duration of US utility-scale batteries was a little over 46 minutes in 2015 and had doubled to 1.5 hours by 2019.[14] Falling costs helped: average battery capital costs were 589 dollars per kWh in 2019, after a 72% fall since 2015, and cheaper energy capacity lets each site run longer at full power.[15] By mid-2026 the US had nearly 52 GW of battery storage power capacity in operation.[16]

    Round-trip efficiency

    No battery gives back everything put into it. Some energy is always lost when storing and retrieving it.[17] The share that comes back is called round-trip efficiency. In 2019 the US utility-scale battery fleet averaged 82%, slightly better than pumped hydro storage at 79%.[18]

    Round-trip efficiency is the percentage of electricity put into storage that is later retrieved. In 2019 the US battery fleet averaged a monthly round-trip efficiency of 82%, against 79% for pumped storage.[18] So a battery cannot return every kWh it was charged with.[18]

    Reading a battery announcement

    • Two numbers, two units. “100 MW / 400 MWh” means 100 MW of power and 400 MWh of energy, a four-hour battery under EIA’s definition.[3]
    • Not all capacity is for sale. At Hornsdale, only 30 MW and up to 119 MWh were normally available for commercial trading in 2018. The rest was reserved for grid reliability and an emergency protection scheme.[19][20]
    • Cost per kW and cost per kWh are different. A battery cost quoted per kWh refers to energy capacity.[15]

    The first example in the list above is a worked illustration of the duration formula, not a specific project. Home-battery sizing is covered in Home battery storage explained, and grid uses in How grid-scale energy storage works.

    Next in the crash course

    More in Batteries and energy storage

    Developing in Science & Energy

    Go deeper

    Questions readers ask

    What is the difference between kW and kWh?

    A kilowatt (kW) is a unit of power, the rate at which electricity flows at a given moment. A kilowatt-hour (kWh) is a unit of energy, one kilowatt sustained for one hour.[1]

    How do you work out how long a battery lasts?

    Divide its energy capacity by its power rating. EIA calculates duration as nameplate megawatt-hours divided by nameplate megawatts.[3]

    How long do grid batteries usually run?

    It depends on their job. In 2019 batteries in the PJM market averaged 45 minutes, for fast frequency regulation, while those in California averaged 4.0 hours, partly because California counts resources toward reliability reserves only if they can run for at least four hours.[11][13]

    Do batteries give back all the electricity put into them?

    No. In 2019 the US utility-scale battery fleet averaged a monthly round-trip efficiency of 82%, meaning about 82% of the electricity stored came back out.[18]

    Sources

    · 20 claims from 6 publishers

    Each numbered claim is a statement we checked against the sources listed with it. Tap a number in the text to see its sources in place.

    1. [1]

      Watts measure power at a given moment, while watthours measure how much electricity is used over time; one kilowatthour is one kilowatt sustained for one hour. confirmedas of 2026-11-21

    2. [2]

      EIA defines a battery site's energy capacity as the maximum energy it can store and its power capacity as the maximum power it can deliver at any moment; at the end of 2019 US large-scale batteries totalled 1,688 MWh of energy capacity and 1,022 MW of power capacity. confirmedas of 2026-11-21

    3. [3]

      EIA calculates a battery's duration by dividing its nameplate energy capacity in megawatthours by its nameplate power capacity in megawatts. confirmedas of 2026-11-21

    4. [4]

      AEMO reported in 2018 that the Hornsdale Power Reserve was rated at 100 MW discharge and 80 MW charge with 129 MWh of storage, about 75 minutes at full discharge. confirmedas of 2018-04-05

    5. [5]

      Electric power is measured in watts; one kilowatt equals 1,000 watts and one megawatt equals 1,000 kilowatts. confirmedas of 2026-11-21

    6. [6]

      A 40-watt light bulb used for five hours uses 200 watthours, or 0.2 kilowatthours, of electrical energy. confirmedas of 2026-11-21

    7. [7]

      Storage is rated by energy capacity, the total energy it can hold (in kilowatt-hours), and power capacity, how much it can release at a given time (in kilowatts). confirmedas of 2026-11-21

    8. [8]

      Rongke Power's 200 MW / 1 GWh vanadium flow battery station in Jimsar County, Xinjiang, was connected to the grid on 28 May 2025, billed as the first gigawatt-hour-scale flow battery. reportedas of 2025-05-29

    9. [9]

      Form Energy says its iron-air system can store and discharge energy for up to 100 hours. confirmedas of 2026-10-10

    10. [10]

      Flow battery energy capacity is raised by enlarging the electrolyte tanks and power by enlarging the reactor, so the two can be sized separately. confirmedas of 2023-04-07

    11. [11]

      In 2019 large-scale batteries in PJM averaged 10.8 MW of power, 6.8 MWh of energy and 45 minutes of duration, serving frequency regulation, while those in California's CAISO averaged 4.7 MW, 14.4 MWh and 4.0 hours, serving reliability. confirmedas of 2026-11-21

    12. [12]

      EIA describes PJM batteries as power-oriented, with larger capacities but shorter durations for frequency regulation, and California batteries as energy-oriented, with small power capacities and long durations for reliability. confirmedas of 2026-11-21

    13. [13]

      The California Public Utilities Commission requires resources to provide at least four hours of output to count toward reliability reserves, so California batteries tend to need larger energy capacities. confirmedas of 2026-11-21

    14. [14]

      The weighted average duration of US utility-scale batteries was a little over 46 minutes in 2015 and had doubled to 1.5 hours by 2019. confirmedas of 2026-11-21

    15. [15]

      Average US battery energy storage capital costs were 589 dollars per kilowatthour in 2019, after a 72% fall between 2015 and 2019, and lower costs allow more energy capacity at each site, lengthening duration at maximum power. confirmedas of 2026-11-21

    16. [16]

      US operational battery storage capacity reached 43.6 gigawatts by the end of 2025 and nearly 52 gigawatts by mid-2026, after average annual growth of 70% over three years. confirmedas of 2026-08-07

    17. [17]

      DOE notes that storage is never 100% efficient, because some energy is lost converting and retrieving it. confirmedas of 2026-11-21

    18. [18]

      Round-trip efficiency is the share of electricity put into storage that is later retrieved; in 2019 the US utility-scale battery fleet averaged a monthly round-trip efficiency of 82%, against 79% for pumped storage. confirmedas of 2026-11-21

    19. [19]

      Under normal conditions 30 MW of the battery's discharge capacity, and up to 119 MWh of its energy, were available to Neoen for commercial operation, while the remaining 70 MW was reserved for power-system reliability and offered at the market price cap. confirmedas of 2018-04-05

    20. [20]

      AEMO reported in 2018 that a System Integrity Protection Scheme, then expected to be fully commissioned in the second quarter of 2018, was intended to detect high flows on the Heywood Interconnector and trigger the battery to discharge at 100 MW as quickly as possible, with 10 MWh of its storage reserved for the scheme. confirmedas of 2018-04-05